(Message inbox:5379) Date: Mon, 31 Jan 2005 15:20:46 MST To: "Timothy L. Thomas" , download@hpc.unm.edu, Aron Warren , Roy Heimbach From: Jim Prewett Subject: Power/Cooling/Space requirements (fwd) ---------- Forwarded message ---------- Date: Mon, 31 Jan 2005 14:19:23 -0800 From: Danielle Conner To: download@ahpcc.unm.edu Subject: Power/Cooling/Space requirements Hi Jim, Please read below. Just let me know if you have any questions or concerns. Danielle Conner Linux Networx 510-996-2976 - office 510-749-0166 - cell dconner@lnxi.com ============================================================================== Here is the information for quote # 9307 - (16 node system) Total Watts 6,507.2 Total lbs 1,041.4 Total Amps 54.2 Total Kg 472.4 BTU/hr 22,202.6 Cooling Tons 1.9 Volts = 120 TF 1.076 UPS KVA = 9.3 ft3/min 764.2 3-phase A 33.0 m3/min 21.6 ============================================================================== Here is the information for quote # 0591 - (64 node system) Total Watts 24,819.0 Total lbs 2,811.6 Total Amps 206.8 Total Kg 1,275.3 BTU/hr 84,682.4 Cooling Tons 7.1 Volts = 120 TF 1.076 UPS KVA = 35.5 ft3/min 2914.9 3-phase A 125.8 m3/min 82.5 ==============================================================================